Part Number: ETI0001-2275
Rugged MilSpec Rack or Fixed Mount
2000 VA UPS & Frequency Converter
1400 Watt (1.9 Hp) Commercial/Industrial 2 kVA MilSpec UPS with a Variety of Power Levels Available
& Frequency Converter used in Shelters and
Wind Turbine
Applications.
Rugged
Rack or Fixed Mount Unit w/ Reduced Depth and Removable Low Cost Battery Module

ETI0001-2275 Rugged MilSpec UPS Standard Front Panel Layout

ETI0001-2275
Rugged MilSpec UPS Standard Right Panel Layout
The
field proven PowerStation UPS line is ideally suited
for military, industrial, computer and telecommunications
applications requiring high reliability, rugged construction,
compact size and light weight design. These units are equally
suited for use in shipboard, airborne, vehicular, field
deployed or fixed locations with controlled or uncontrolled
environments. The "ETI0001-2275" is being used
a because of their stringent performance and reliability
requirements.
The
heavy-duty chassis, occupying only 6.967" (4U) of
rack space and 15.68" depth, has rounded metal corners
and rugged handles right and left, aiding in safe handling.
Internally, all major components are well secured and electrically
insulated to prevent damage due to shock and vibration.
The
internal shielded input transformer provides galvanic isolation
with provisions for domestic (120 VAC, CONUS) and optionally
for international (230 VAC, OCONUS) input voltages. Special
EMI/RFI filters and input power factor correction minimize
both input current and harmonics. The unit also operates
as a frequency converter, taking 46-70 hertz input and
converting it to clean, uninterruptible 60 hertz power.
The input switch and the galvanic isolation transformer
all provide a double pole isolated source for shipboard
systems or overseas locations where phase references and
grounding are not consistent.
The
LED arrays keep the operator informed as to the unit's
status including load and battery levels. The high intensity
audible alarm can be heard in high noise environments.
All controls and protective devices are brought to the
front and rear panels with critical switches having finger
guards. Further, all front panel devices are recessed to
prevent damage or accidental operation. Various optional
power distribution controls are available which mount on
the front panel or remotely.
The
right panel provides locking connectors for the input and
output power. Multiple input and output power panel options
are available. Removable and washable air filters and a
high capacity stainless steel ball bearing fans provide
added protection in both controlled and hostile environments.
The exhaust air is diverted out the rear vent, with alternate
air flow directions optional. The batteries are maintenance
free with immobilized electrolyte and are constructed of
flame retardant materials. For more information, see the Battery
Technology section. The Status connector provides
an interface with optional computer software
providing loss of AC and low battery status
as well as remote shut down capability.
See
the Power Distribution
Units section for a listing of stand alone PDUs. See
the N5 Series ETI0001-1482 for
a version of this UPS with an integrated PDU and remote
control.
Overall,
the PowerStation line is uniquely qualified for critical
shipboard, vehicle, airborne or land based systems combining
advanced modular design features with highly reliable construction.
|
Technical Specifications: P/N:
ETI0001-2275
| AC
INPUT |
| Nominal
voltage: UPS |
Nominal
120 VAC, optional autoranging input of 85-270 VAC |
| Voltage
Range: UPS |
85-140
VAC @ full load without using battery, to 70 VAC
@ 75% load |
| Current
(max): UPS |
14A |
| Frequency:
UPS |
From
50 Hz to 60 Hz standard,+/_5% |
| Efficiency:
UPS |
>86% |
| Power
Factor: UPS |
>0.95% |
| AC
OUTPUT |
| VA
rating: |
2000
VA |
| Power
Factor (Resistive Load) |
1400
W |
|
Voltage
(Selectable): |
110
V |
| 115
V |
| 120
V |
|
Frequency: |
50/60
Hz (auto tracking) |
| Voltage
Regulation: |
+/_
@% |
| Frequency
Stability: |
+/_
0.3% (Battery mode) |
| Step
Load Change: |
+/_
7% for 100% Load Variation |
| Harmonic
Distortion: |
Linear
Load <3%
Non-Linear Load <5% |
| Overload |
105%
load for 50 seconds |
| Crest
Ratio |
3:1 |
| INTERNAL
BATTERY |
| DC
Voltage |
72V |
| Type |
12V,
7AH Sealed Lead Acid |
| Backup
Time |
Full
Load: 7 min. typ.
Half Load: 20 min. typ. |
| Recharge
Time |
8
Hours to 90% |
| Transfer
Time |
| Line
Fails/Recovers |
Zero
Time - True online, no transfer for brownoutor blackout |
| UPS-
Bypass/Reverse |
<4
ms for bypass transfers |
| After
Overload |
Auto
Transfer to UPS |
| Audible
Noise |
@
1 Meter |
<_55dBA |
| Indicators |
L.E.D. |
Line,
Inverter, Battery Reserve, Load, Bypass, Alarm, Crest,
Battery & Load Capacity Level |
| Audible
Alarms |
|
DC
Mode, Low Battery, Over/Under Voltage, Over/Under
Frequency, High Temperature, Over Load, Alarm. |
| Interface |
Computer |
RS-232
(Supports RUPSII, UPSILON & SEC protocols) |
|
Environment |
|
Temperature |
0°C-40°C
(32°F - 104°F) |
|
Humidity |
10%
- 95% Non-condensing |
|
MECHANICAL |
| Input
Line 120V |
6
Foot Cord with NEMA L5-20 Plug |
| Output
120V |
(2)
NEMA 5-15R, (1) CPC, PNL, SOC, S3, 17-3 |
Unit
weight:
|
68.4
lb. (31kg) |
|
Approvals |
Agency
|
UL,
CUL, FCC Class A, (CE on specified models only) |
| OPTIONAL
ACCESSORIES |
| |
Autoranging
International Input, Cold Start, Emergency Power
Off, Elapsed Time Meter, Alternate I/O Configurations,
Dual Source Input, Battery
Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power
Distribution Units, Software
Interface, Asynchronous serial COM port,
10BaseT Ethernet SNMP/HTTP port, Transport
Cases, Slides and Mounting
Kits |
1)
European CE Certification Only.
2) Isolation Transformer.
3) Backup time is for reference only. Actual duration
may vary depending on temperature, battery condition
and type of load.
4) Contact Factory for 120V settings.
5) Factory Default Settings.
|
|
|
|
| |
|
|
|
|
 |
|
 |
|